Manual Control Level - Omron E5AN-H User Manual

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Performing Manual Control
Manual MV Limit
Enable
Moving from the
Operation Level to the

Manual Control Level

Press O key for at least 1 s.
Manual Control Level
C
25.0
20.0
PV/MV
(2) For Manual MV Limit Enable, this value will be between the MV upper limit
and the MV lower limit.
(3) This setting is enabled only when the Direct Setting of Position Propor-
tional MV parameter is set to ON.
When the Manual MV Limit Enable parameter is set to ON (enabled), the MV
limits will function and the setting range for the Manual MV parameter will be
between the MV upper limit and the MV lower limit. When the parameter is set
to OFF (disabled), MV limits will not function.
Parameter name
Manual MV Limit
OFF: Disabled, ON: Enabled
Enable
• When the O Key is pressed for at least 3 seconds in the operation level's
auto/manual switching display, the manual mode will be entered and the
manual control level will be displayed. It is not possible to move to any dis-
plays except for the PV/MV parameter during manual operation. Press the
O Key for at least one second from the PV/MV parameter display in man-
ual control level to return to automatic mode and display the top parame-
ter in the operation level.
a-m
Press O key for at least
3 s.
a-m display flashes for
at least 1 s.
• If an event input is set to MANU (auto/manual), the Auto/Manual Switch
parameter will not be displayed. Use the event input to switch between
automatic and manual modes.
Setting range
Operation Level
C
25.0
PV
M
C
25.0
PV/SP
100.0
M
a-m
Auto/Manual Switch
M
bank
Bank No.
0
M
Section 4-13
Default
ON
121