Setting Output Specifications
Example: E5CN-H
Parameter name
Symbol
out1
Control Output 1
Assignment
out2
Control Output 2
Assignment
sub1
Auxiliary Output 1
Assignment
sub2
Auxiliary Output 2
Assignment
Note
Operating Procedure
Operation Level
PV/SP
C
25.0
100.0
Initial Setting Level
Input Type
in-t
5
Initial Setting Level
Standard or
5-hc
Heating/Cooling
stnd
54
Parameter name
Auxiliary Output 2 Assignment
Auxiliary Output 3 Assignment
(E5AN/EN-H only)
• Each output is automatically initialized as shown below by changing the
control mode.
Without control output 2
Standard
Control output
(heating)
Not assigned.
(See note 1.)
Alarm 1
(See note 2.)
Alarm 2
(1) There is no control output 2 and no parameter assignment is displayed
for that output.
(2) The Auxiliary Output 1 Assignment parameter becomes the program end
output unless the Program Pattern parameter is set to OFF.
■ Alarms
It will be specified in this section when an alarm must be assigned, i.e., when
an alarm must be set for the Control Output 1 or 2 Assignment parameters, or
for the Auxiliary Output 1 or 3 Assignment parameters. For example, if alarm 1
is set for the Control Output 1 Assignment parameter, then alarm 1 has been
assigned.
Assigning a work bit to either control output 1 or 2 or to auxiliary output 1 to 3
is also considered to be the same as assigning an alarm. For example, if work
bit 1 is set for the Auxiliary Output 1 Assignment parameter, then alarms 1 to 3
have been assigned.
This procedure sets the following control and auxiliary output assignments.
Control output 1: Control output (heating); Control output 2: Control output
(cooling); Auxiliary output 1: Alarm 1; Auxiliary output 2: Alarm 2
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Standard or Heating/Cooling parameter by pressing the M
Key.
Symbol
sub2
sub3
Heating/cooling
Control output
Control output
(heating)
(heating)
Not assigned.
Not assigned.
(See note 1.)
Alarm 1
Alarm 1
(See note 2.)
(See note 2.)
Control output
Alarm 2
(cooling)
Section 3-5
Initial status
Alarm 2
Alarm 3
With control output 2
Standard
Heating/cooling
Control output
(heating)
Control output
(cooling)
Alarm 1
(See note 2.)
Alarm 2