4-1-2

General Parameter Group

This section describes parameters in the general parameter group.
Item
S Output Error Latch Time 0 to 65,530 ms
S Input Error Latch Time
Test Output Idle State
Unit Name
Threshold Network
Power Voltage
4-1 Editing Parameters
Settings
Description
This parameter is common to all the
safety outputs.
(in 10-ms increments)
It sets the time to latch the error state
when an error occurs in these outputs.
Even when the cause of the error has
been removed, the error state will re-
main latched for the time set here.
0 to 65,530 ms
This parameter is common to all safety
inputs and test outputs.
(in 10-ms increments)
It sets the time to latch the error state
when an error occurs in these inputs/
outputs. Even when the cause of the
error has been removed, the error
state will remain latched for the time
set here.
Clear off
This parameter is common to all test
outputs for which the Test Output
Channel Mode is set to Standard Out-
put.
Keep output data
It sets the output state of the test out-
put when idle data is received.
32 characters max.
This parameter sets a user-chosen
name for the Safety I/O Terminal. The
set name is saved in the Safety I/O
Terminal and displayed in the network
configuration.
8.0 to 30.0 V
This parameter sets the threshold of
the network power voltage. When the
voltage falls below the set threshold
voltage, the corresponding bit in gen-
eral status turns ON.
Default
1,000 ms
1,000 ms
Clear off
None
11.0 V
71