The discrepancy time can be set between 0 and 65,530 ms in 10-ms increments.
Channel Mode
Single Channel
Dual Channel Equivalent
Dual Channel Complementary
5-4-2

Setting Test Outputs

Click the Local IN/Test Output Tab and then Test Output Tab in the window to set the test outputs.
Error Latch Time
The test output is used in combination with a safety input. The same error latch time setting is thus used for
all safety inputs. Refer to Error Latch Time in 5-4-1 Setting Safety Inputs (page 90).
Settings for Individual Test Outputs
Double-click the row of the test output number to set, or select the row and click the Edit Button.
Terminal Name
Set the terminal name for the test output. The terminal name set here is used as the I/O tag in the Logic Ed-
itor.
92
Description
Specifies using Single Channel Mode.
If Single Channel is selected, the Safety Input Terminal to be paired in
the Dual Channel setting will also be set to Single Channel Mode.
Specifies using the Dual Channel Equivalent Mode with a paired Safety
Input Terminal.
Specifies using Dual Channel Complementary Mode with a paired
Safety Input.
Section 5: Editing Safety Network Controller Parameters