Displaying the C/CV I/O Table Window

The C/CV I/O Table Window is displayed when the PLC is not a CS/CJ/CP-series PLC.
Rack's starting CIO address

Unit Settings

Settings for the CS/CJ/CP I/O Table Window

The CS/CJ/CP I/O Table Window is displayed when the PLC is a CS/CJ/CP-series PLC.
Creating an IO Table
Creation of an IO Table whilst connected to a PLC causes the Actual IO Table in the hardware to be written to the
Registered IO Table. An IO Table can also be edited offline and stored to file, this method is usually employed
when designing a PLC's IO Table.
To create an IO Table, select Create from the Options menu.
Slot Allocation
The following procedure shows how to edit the I/O table in the I/O Table Window.
When Units which do not have CPS are registered in the I/O tables, the current
consumption and width cannot be calculated correctly. In this case, estimated values
marked with "*" are displayed for the current consumption and width as shown below.
Specifically, when a previous model of a Unit (such as C200H I/O Units) is used,
estimated values may be displayed.
In this case, check the current consumption and width in the Operation Manual of the
Unit.
Online, the current status of the DIP switches on the target PLC (CPU Unit) can be
checked by selecting Options - DipSwitch Information.
Slot number
Unit's starting CIO address
Rack number
CHAPTER 3 – IO Table Component
Special I/O
Unit's unit
number
Number of output words and
number of input words
Unit name
PART 2: CX-Server PLC Tools
CX-Server PLC Tools_ Page 23