PART 3: CX-Server Runtime
CHAPTER 3 – Communications
Toolbus
Toolbus operates in a similar manner to SYSMAC WAY. The connection is made to a PLC using its peripheral
port.
The following connection is required:
♦ RS232 connection via a standard serial port on the computer (COM1 etc.) using either CIF01 or CIF02
cable.
The Driver tab is similar to that belonging to SYSMAC WAY; however, for some PLCs fixed values are
entered and these cannot be altered (see table below). The CS/CJ/CP-Series PLC Toolbus configuration ensures
successful connection to the PLC every time, independently of the rate specified by the user provided the Auto
Baud Rate Detection setting has been checked.
Serial Networks
When connecting a computer to a serial network of PLCs, each PLC needs to be configured so that it has a
different Unit number. The Unit number for C-series PLCs should be configured as follows:
The Unit number for CV-series PLCs and CS/CJ-series PLCs should be configured as follows:
Online connection is possible through a Serial Communications Board or Unit with unit version 1.2
or later mounted to a PLC directly connected via the peripheral bus (Toolbus) or Host Link (or to a
CX-Server Runtime_Page 20
2. In the Network tab, check the Unit No, usually 0 for connecting to a single PLC or the
multi drop number for an RS422 connection.
3. In the Driver tab, check the port on the computer for connection to the PLC and enter it in
the Port Name field.
Select the Baud Rate, Parity, Data Bits and Stop Bits from the drop-down lists available
4.
for the selected port.
For the Modem tab, refer to Microsoft Windows documentation.
5.
Select the OK pushbutton to save these settings, or select the Cancel pushbutton to abort
6.
the operation.
Note:
For CS/CJ/CP-series PLCs, SYSMAC WAY dip switch five on the front panel must
be set to 'OFF'.
PLC
Fixed
CS/CJ/CP Series
Yes
CV/CVM Series
Yes
C Series
No
CPM1/CPM1A
- - -
SRM1/SRM1-V2
- - -
CPM"*/CPM2*-S*
- - -
CQM1/CQM1H
- - -
CPU-mounted Host Link unit:
Rack-mounted Host Link unit:
Direct CPU RS232 port:
Direct CPU Peripheral port:
Rack-mounted Host Link unit:
Direct CPU RS232 port:
Direct CPU Peripheral port:
Remote SYSBUS/2 Peripheral port:
Note:
The unit number rotary switches on the top of CV-series SIO units are the unit
number of that Special I/O Unit on that PLC rack and not the Unit number of the PLC
on the serial network.
Data Bits
Parity
8
None
8
Odd
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
DIP switches on back of unit
Rotary switches on front of unit
Internal DM settings
Internal DM settings
Unit Setup dialog
Host Link settings dialog
Fixed as Unit 0
Fixed as Unit 0
Stop Bits
1
1
- - -
- - -
- - -
- - -
- - -
OMRON
Revision 2.0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents