Specifications - Omron CQM1 Operation Manual

Sysmac cqm1h/cqm1 series dedicated i/o units
Hide thumbs Also See for CQM1:
Table of Contents

Advertisement

Specifications

2-2
Specifications
General Specifications
Performance Specifications
Item
Sensor type (See previous page for
temperature ranges.)
Number of control loops
Control output
Control mode
Setting and display accuracy
Hysteresis adjustment
Proportional band
Derivative time
Integral time
Manual manipulated variable
Control period
Input shift value
Sampling period
Output refresh period
Current consumption
Weight
Dimensions
• The IOTC(––) instruction can be used to simplify programming when
using CX-Programmer version 2.0 or higher and a CQM1H CPU Unit with
a lot number of 0160 or later.
The general specifications of the CQM1-TC20@/TC30@ conform to those of
the CQM1H/CQM1 Series.
Units for thermocouples
K, J, T, L, R, S, B
2 loops or 4 loops (2-loop model has heater burnout alarm)
NPN or PNP output with short-circuit protection
Power supply voltage: 24 VDC
Maximum switching capacity: 100 mA per output
Leakage current: 0.1 mA max.
Residual voltage: 0.8 V max.
ON/OFF control, advanced PID control (2 degrees of freedom), or manual oper-
ation
C Ranges
(Process value 0.3% or 1 C, which-
ever is larger) 1 digit max.
F Ranges
(Process value 0.3% or 2 F, which-
ever is larger) 1 digit max. (See note
1.)
The accuracy is given when the cold
junction compensator on the terminal
block is used. Always use the cold junc-
tion compensator on the terminal block.
(See note 2.)
0.1 to 999.9 C/ F (0.1 C/ F unit)
0.1 to 999.9 C/ F (0.1 C/ F unit)
0 to 3,999 s (1 s unit)
0 to 3,999 s (1 s unit)
0.0 to 100.0% (0.1% unit)
1 to 99 s (1 s unit)
–99.9 to 999.9 C/ F (0.1 C/ F unit)
0.5 s
0.5 s
190 mA max. at 5 VDC
200 g max.
32 x 110 x 107 mm (W x H x D)
Note
1. The accuracy of K and J thermocouples at or below –100 C is 2 C 1
digit max., and the accuracy of R and S thermocouples at or below 200 C
Specification
(CQM1-TC20@)
+10%
/
–15%
Section 2-2
Units for platinum resistance
thermometers (CQM1-TC30@)
Pt100, JPt100
0.1 C Ranges
(Process value 0.3% or 0.8 C,
whichever is larger) 1 digit max.
0.1 F Ranges
(Process value 0.3% or 1.6 F,
whichever is larger) 1 digit max. (See
note 1.)
0.01 C Ranges
(Process value 0.3% or 0.5 C,
whichever is larger) 1 digit max.
0.1 C Ranges
–99.9 to 999.9 C/ F (0.1 C/ F unit)
0.01 C Ranges
–9.99 to 99.99 C/ F (0.01 C/ F unit)
245