Programming and Adjustment
–10 to 10 V
1,2,3...
100
4. Use the peripheral device to monitor the word to which the analog input
data to be adjusted is stored. The CQM1H/CQM1 can be in any mode. The
analog input conversion data will be the lower-limit value.
5. Apply the same method to the analog input's maximum value to obtain the
upper-limit value.
6. Create the following program to scale values in a range between the lower
and upper-limit values and designate the lower- and upper-limit values that
have been monitored as parameters. Refer to page 96, Scaling for details.
00000
* "n" indicates the allocated word for analog input.
DM 0100
DM 0101
DM 0102
DM 0103
If the Analog Input Unit is set to a range of –10 to 10 V, follow the steps
described below to adjust the Analog Input Unit.
1. Refer to 3-1 Settings and connect the Analog Input Unit, CPU, and sensor
or transducer.
2. Connect a peripheral device such as a Programming Console to the CPU
and while referring to 3-3-1 Programming, create a program to convert 2's
complement.
Peripheral device
Sensing object
00000
Input condition
* "n" indicates the allocated word for analog input.
Set value
0000
(BCD)
(Hexadecimal)
Lower limit value
0100
(BCD)
(Hexadecimal)
Upper limit value
PS
CPU
OUT
IPS
IN
Sensor or transducer
Section 3-3
SCL(66)
*
n
DM 0100
DM 0000
AD
AD
OUT
ANDW(34)
#0FFF
n
DM 0200
XORW(36)
#0800
DM 0200
DM 0200