Features and Word Allocations
2-1
Features and Word Allocations
2-1-1
Features
Temperature Control Units
Temperature Ranges
K (CA)
K (CA)
1800
1600
1300
1300
800
500.0
600
400
300
200
100
0
0.0
100
200
200
Code
0
1
No.
Min.
1 C
0.1 C
unit
2-1-2
Word Allocations
244
• The PID with advanced feed-forward circuitry (2 degrees of freedom) of
the CQM1-TC20@/TC30@ assures stable temperature control. The Units
can also be set to ON/OFF control.
• Temperature Control Units are available for either 4-loop temperature con-
trol or 2-loop temperature control, and Units with 2-loop temperature con-
trol provide a heater burnout alarm. You can also select between
thermocouples or platinum resistance thermometers as the input sensors.
4 loops
2 loops with heater
burnout alarm
Thermocouples (See note.)
J (IC)
J (IC)
T (CC)
L
850
850
400.0
400.0
0.0
100
100
200.0
2
3
4
5
1 C
0.1 C 0.1 C
1 C
Note K (CA) = Chromel/alumel, J (IC) = Iron/constantan, T (CC) = Copper/constan-
tan, L = Iron/constantan, R = Platinum/platinum rhodium 13%, S = Platinum/
platinum rhodium 10%, B = Platinum rhodium 30%/platinum rhodium 6%
• One word each is allocated to the Temperature Control Unit for inputs and
outputs.
• Commands are used to set and read data.
Inputs
Thermocouples
Platinum resistance
thermometers
Thermocouples
Platinum resistance
thermometers
L
R
S
B
1700
1700
1800
400.0
100
0.0
0
0
6
7
8
9
0.1 C 1 C
Section 2-1
Output type
NPN outputs
PNP outputs
CQM1-TC201
CQM1-TC202
CQM1-TC301
CQM1-TC302
CQM1-TC203
CQM1-TC204
CQM1-TC303
CQM1-TC304
Platinum resistance
thermometers
Pt100
JPt100
Pt100
650.0
650.0
250.0
20.0
200.0
200.0
0
1
2
0.1 C
0.01 C
JPt100
---
250.0
20.0
3
4 to
9
---
Need help?
Do you have a question about the CQM1 and is the answer not in the manual?
Questions and answers