Switch Settings
Timing Charts
Timer selector set to OFF (0ms)
Operation mode selector set to L on (Light
ON)
Light received
Light not received
Operation indicator
ON
(orange)
OFF
ON
Control output
OFF
Operation mode selector set to D on (Dark
ON)
Light received
Light not received
ON
Operation indicator
(orange)
OFF
ON
Control output
OFF
Mode Selector
2-2-2

E2C-MA11 Proximity Sensor Module

Cable Length Switches
Sensor
E2C-CR8A
Position of the
E2C-CR8B
switches of the
E2C-X1A
Amplifier Unit
E2C-C1A
E2C-X1R5A
Timer Switch
Note The operation mode selector and timer selector must be set before mounting
the E3X-MA11 to the Sensor Unit.
Setting
RUN
SET
Set the switches as shown below to the length of sensor cable being used
either for standard cable lengths or after cutting the cable.
0 to 1 m
A
C
B
D
Knob
position
Note
1. If two cables of the same length and diameter are being attached together
in parallel, position one of the cables 1 m above or below the other.
2. Set all switches to the right for the E2C-CR5B.
Setting
0 ms
10 ms
Timer selector set to ON (10 ms)
Operation mode selector set to L on (Light
ON)
Light received
Light not received
Operation indicator
(orange)
Control output
Operation mode selector set to D on (Dark
ON)
Light received
Light not received
Operation indicator
(orange)
Control output
Normal operation
Axis adjustment or sensitivity adjustment (teaching).
Cable length
1 to 2 m
2 to 3 m
A
C
A
C
B
D
B
D
No timer
10-ms Off-delay timer active
Section 2-2
ON
OFF
ON
OFF
10 ms
ON
OFF
ON
OFF
10 ms
Function
3 to 4 m
4 to 5 m
A
C
A
B
D
B
Function
C
D
143