Commands and Responses
7-3-13 Present Value Read
Command
Command Code
Parameter
Response
This command can be used only when the timing hold in operation mode A is
set to normal.
This command is used to read the present measured value after scaling.
Parameters are not used with this command.
If the correct command code or parameter is set to the output word, the
present conversion data will be set to the input word.
If the wrong command code or parameter is set to the output word, one of the
following error codes will be set to the input word.
E000: This error code will be set to the input word if a nonexisting command
code is used.
E003: This error code will be set to the input word if the mode designation for
this command is not correct.
Section 7-3
Sign
0: Positive
F: Negative
Value
Range: 0 to 9999
227