System Configuration

1-2
System Configuration
Power Supply
Word Number
CQM1H/CQM1-series
CPU
Sensor input
(V INPUT/I INPUT)
Timing input
(T/G)
• Use the Programming Console to write its initial values to the Unit.
• The Unit needs zero input and zero reset input for forced zero.
• The CQM1-LSE01 does not have monitor output.
The word allocations for a CQM1H/CQM1-series Dedicated I/O Unit are as
follows.
Input:
001 to 015
Output: 100 to 115
The Unit uses a single input word and single output word. The CQM1-LSE01,
which is not provided with the monitor output function, also uses a single out-
put word.
Words are allocated in left-to-right order to the CQM1H/CQM1-series Dedi-
cated I/O Units mounted to the PC. For example, if an Input Unit that occupies
one word, an Output Unit that occupies two words, and the CQM1-LSE01/
LSE02 are mounted to the PC and if the Input Unit and Output Unit are
located to the left of the CQM1-LSE01/LSE02, the input and output word
numbers of the CQM1-LSE01/LSE02 will be 002 and 102 respectively.
Input word
Output word
Output Unit located
on the left side
Linear Sensor
Interface
Monitor output
(OUTPUT)
Input Unit located on the left side
CPU
CQM1-LSE01/LSE02
Section 1-2
Other Units
to
to
179