Connections to B7A Link Terminals

3-1
Connections to B7A Link Terminals
3-1-1
Recommended Cables
Standard Transmission Delay-time Type
Cabtire Cable
Rapid Transmission Delay-time Type
Shielded Cable
!Caution If shielded cable is not used for the high-speed transmission delay-time Link
3-1-2
Connecting Terminals
CQM1-B7A21
CQM1-B7A13
20
The B7A Interface Unit can be connected to the input and output B7A Link
Terminals using the following cables.
Use a VCTF 0.75 x 3 C cabtire cable (100 m max.) if a power supply is shared
and a VCTF 0.75 x 2 C cabtire cable (500 m max.) if power is supplied inde-
pendently.
Use a 0.75 x 3 C shielded cable (50 m max.) if a power supply is shared and a
0.75 x 2 C shielded cable (100 m max.) if power is supplied independently.
Terminal, the transmission distance is not to exceed 10 m regardless of
whether power supply is shared or wired separately.
Connect the input and output B7A Link Terminals to the B7A Interface Unit via
the following terminals using crimp-style terminals used for CQM1H/CQM1 I/
O Units.
B
0
A
0
B
1
A
1
B
2
Unused
A
2
B
3
A
3
B
0
A
0
B
1
A
1
B
2
Unused
A
2
B
3
A
3
Connect to the SIG terminal of
the output B7A Link terminal.
Connect to the negative power supply ter-
minal of the output B7A Link Terminal.
Connect to the SIG terminal of
the input B7A Link Terminal.
Connect to the negative power supply ter-
minal of the input B7A Link Terminal.
Connect to the SIG terminal of
the input B7A Link terminal.
Connect to the negative power supply ter-
minal of the input B7A Link Terminal.
Connect to the SIG terminal of
the input B7A Link Terminal.
Connect to the negative power supply ter-
minal of the input B7A Link Terminal.
Section 3-1
Word m
Word n
Word n
Word n + 1