9 PARAMETERS SETTING

In HGM9610 controller, there are no items of mains in setting and also no mains items in configurable
ports of input/output.
CAUTION: Please change the controller parameters when generator is in standby mode only (e. g. Crank disconnect
conditions selection, configurable input, configurable output, various delay), otherwise, shutdown and other abnormal
conditions may happen.
NOTE: Maximum set value must over minimum set value in case that the condition of too high as well as too low will
happen.
NOTE: When setting the warning alarm, please set the correct return value; otherwise, maybe there is abnormal alarm.
When setting the maximum value, the return value must less than set value; When setting the minimum value, the return
value must over set value.
NOTE: Please set the generator frequency value as low as possible when cranking, in order to make the starter be
separated quickly as soon as crank disconnect.
NOTE: Configurable input could not be set as same items; otherwise, there are abnormal functions. However, the
configurable output can be set as same items.