No.
Function
15
Aux. Input 6
16
Magnetic Pickup
17
MP 2
18
MP 1
19
Aux. Input 7
20
21
Aux. Output 4
22
23
ECU CAN
24
ECU CAN H
25
ECU CAN L
26
RESERVE
33
RS485
34
RS485-
35
RS485+
36
37
Aux. Output 5
38
39
Aux. Output 6
40
41
Mains Voltage L1
42
Mains Voltage L2
43
Mains Voltage L3
44
Mains Voltage N
45
Genset Voltage L1
46
Genset Voltage L2
47
Genset Voltage L3
48
Genset Voltage N
49
CT1
50
CT2
51
CT3
52
CT COM
HGM9600 Series Genset Controller User Manual
Cable Size
1.0mm
2
Ground connected is active (B-)
Connected with Speed sensor, shielding line is
0.5mm
2
recommended. (B-) has already connected with speed
sensor 2
1.0mm
2
Ground connected is active (B-)
Normally close output, rated 7A
1.5mm
2
Public points of relay
Normally close output, rated 7A
/
Impedance-120Ω shielding wire is recommended, its
0.5mm
2
single-end earthed.
0.5mm
2
/
Empty terminal
/
Impedance-120Ω shielding wire is recommended, its
2
0.5mm
single-end earthed
0.5mm
2
2.5mm
2
Normally close output, rated 7A
2.5mm
2
Normally close output, rated 7A
2
2.5mm
Public points of relay
2.5mm
2
Normally close output, rated 7A
2.5mm
2
Public points of relay
Connected to
2
1.0mm
recommended) (HGM9610 without)
Connected to
1.0mm
2
recommended) (HGM9610 without)
Connected to
1.0mm
2
recommended) (HGM9610 without)
1.0mm
2
Connected to N-wire of mains (HGM9610 without)
Connected to A-phase of gen-set (2A fuse is
2
1.0mm
recommended)
Connected to B-phase of gen-set (2A fuse is
1.0mm
2
recommended)
Connected to C-phase of gen-set (2A fuse is
1.0mm
2
recommended)
1.0mm
2
Connected to N-wire of gen-set
Outside connected to secondary coil of current
1.5mm
2
transformer (rated 5A)
Outside connected to secondary coil of current
1.5mm
2
transformer (rated 5A)
Outside connected to secondary coil of current
1.5mm
2
transformer (rated 5A)
1.5mm
2
See following installation instruction
Remarks
Details see Table
15
Details see Table
14
Details see Table
14
A-phase of mains
B-phase of
mains
C-phase of mains
Page 30 of 73
(2A fuse is
(2A
fuse is
(2A fuse is