Parameters Setting; Parameters Regulation; Restore Factory Settings; Eliminate Accumulated Time - Smartgen MGC100 User Manual

Petrol genset controller
Table of Contents

Advertisement

8 PARAMETERS SETTING

8.1 PARAMETERS REGULATION

When the controller is running, press
will display
1)
Press
2)
After parameter number is selected, press
and
3)
Press
4)
For multiple parameters, step (1-3) can be repeat done for setting;
5)
After parameter setting, press

8.2 RESTORE FACTORY SETTINGS

In emergency stop input status, press
default and "reset" will be displayed on LED.

8.3 ELIMINATE ACCUMULATED TIME

Press
and
be displayed on LED.
NOTE:
——Over voltage threshold must be greater than under voltage threshold.
——When start successfully, generator frequency need to be set lower as soon as possible in order to starter
separate sooner.
——Number of setting contents refers to "Parameter Content and Range (Table 7)".
——Only in parameter number menu can exit from parameter setting status. If there is no press operation in
parameter number menu, it will exit in 30s automatically.
MGC100 Petrol Genset Controller User Manual
:
and
to downturn/upturn parameter number;
to increase/decrease parameter value (it can be double-clicked);
to confirm modification and save value;
for 5s at the same time, accumulated running time will be reset an "hclr" will
for 3s, it will enter into parameter number menu and LED
to enter into parameter setting menu; press
for 3s to exit parameter setting status.
and
for 5s at the same time, it can restore to
Page 14 of 16