Smartgen HGM9600 Series User Manual page 9

Genset controller
Table of Contents

Advertisement

Each phase and average power factor PF
Accumulate total generator power kWh, kvarh, kVAh
For mains, controller has over and under voltage, over and under frequency, loss of phase and phase
sequence wrong detection functions; For generator, controller has over and under voltage, over and
under frequency, loss of phase, phase sequence wrong, over and reverse power, over current
functions;
3 fixed analog sensors (temperature, oil pressure and level) are fitted;
2 configurable sensors can be set as sensor of temperature, oil pressure or fuel level;
Precision measure and display parameters about engine,
Temp. (WT)
Oil pressure (OP)
Fuel level (FL)
Speed (SPD)
Voltage of Battery (VB)
Voltage of Charger (VD)
Hour count (HC) can accumulate to max. 65535 hours.
Start times can accumulate to max. 65535 times.
Protection: automatic start/stop of the gen-set, ATS (Auto Transfer Switch) control with perfect fault
indication and protection function;
All output ports are relay-out;
Parameter setting: parameters can be modified and stored in internal EEPROM memory and cannot
be lost even in case of power outage; most of them can be adjusted via front panel of the controller
and all of them can be modified with PC via USB, RS485 or ETHERNET ports.
More kinds of curves of temperature, oil pressure, fuel level can be used directly and users can
define the sensor curves by themselves;
Multiple crank disconnect conditions (speed sensor, oil pressure, generator frequency) are optional;
Widely power supply range DC(8~35)V, suitable for different starting battery voltage environment;
Event log, real-time clock, scheduled start & stop generator (can be set as start genset once a
day/week/month whether with load or not);
Can be used on pumping units and as an indicating instrument (indication and alarm are enabled,
relay is inhibited);
Accumulative total run time and total electric energy of A and B. Users can reset it as 0 and
re-accumulate the value which make convenience to users to count the total value as their wish;
Can control engine heater, cooler and fuel pump;
With maintenance function. Actions (warning, shutdown or trip and stop) can be set when
HGM9600 Series Genset Controller User Manual
°C/°F both be displayed
kPa/Psi/Bar all be displayed
% (unit)
r/min (unit)
V (unit)
V (unit)
Page 9 of 73