No.
28
Reserved
29
Close Generator
30
Open Breaker
31
Close Mains
32
Reserved
33
Start Relay
34
Fuel Relay
35
Idle Control
36
Raise Speed
37
Drop Speed
38
ETS Control
39
Pulse Drop speed
40
ECU Stop
41
ECU Power
42
Pulse raise speed
43
Crank Success
44
Generator OK
45
Generator Available
46
Mains OK
47
Reserved
48
Common Alarm
49
Common Trip and Stop
50
Common Shutdown
51
Common Trip Alarm
52
Common Warn Alarm
53
Reserved
54
Battery High Volts
55
Battery Low Volts
56
Charge Alt Fail
57
Reserved
58
Reserved
59
Reserved
60
ECU Warn
61
ECU Shutdown
62
ECU Comm. Fail
HGM9600 Series Genset Controller User Manual
Type
Control generator to take load.
Control generator to off load.
Control mains to take load.
Action when genset is cranking and disconnect when
stopped completely.
Used for engine which has idles. Close before starting and
open in warming up delay; Close during stopping idle mode
and open when stop is completed.
Action in warming up delay.
Action between the period from "stop idle" to "failed to stop".
Used for engines with ETS electromagnet. Close when stop
idle is over and open when pre-set "ETS delay" is over.
Active 0.1s when controller enter into stop idle, used for
control part of ECU dropping to idle speed.
Used for ECU engine and control its stop.
Used for ECU engine and control its power.
Active 0.1s when controller enter into warming up delay; used
for control part of ECU raising to normal speed.
Close when detects a successful start signal.
Action when generator is normal.
Action in period of generator ok to hi-speed cooling.
Action when mains normal.
Action when genset common warning, common shutdown,
common trips alarm.
Action when common trip and stop alarm.
Action when common shutdown alarm.
Action when common trips alarm.
Action in common warning alarm.
Action when battery's over voltage warning alarm.
Action when battery's low voltage warning alarm.
Action when charge failure warning alarms.
Indicate ECU sends a warning signal.
Indicate ECU sends a shutdown signal.
Indicate controller not communicates with ECU.
Description
Page 42 of 73

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm9610Hgm9620