PARAMETERS SETTING

CAUTION! Please change the controller parameters when generator is in standby mode only (e. g. Start conditions
selection, configurable input, configurable output, various delay), otherwise, alarming to stop and other abnormal
conditions may happen.
NOTE:
1)
Maximum set value must over minimum set value in case that the condition of too high as well as too low will
happen.
2)
When setting the warning alarm, please set the correct return value; otherwise, maybe there is abnormal alarm.
When setting the maximum value, the return value must less than setting; when setting the minimum value,
the return value must over setting.
3)
Please set the generator frequency value as low as possible when cranking, in order to make the starter be
separated quickly as soon as crank disconnect.
4)
Configurable input could not be set as same items; otherwise, there are abnormal functions. However, the
configurable output can be set as same items.
HGM8151 Genset Parallel Controller User Manual
Page 44 of 66