Parameters Setting - Smartgen HGM8110DC-2 User Manual

Genset controller
Table of Contents

Advertisement

9 PARAMETERS SETTING

:
CAUTION
Please change the controller parameters when generator is in standby mode only (e. g. Crank disconnect
conditions selection, configurable input, configurable output, various delay), otherwise, shutdown or other abnormal conditions
may happen.
NOTE:
1) Maximum set value must be over minimum set value in case that the condition of too high as well as too low will happen.
2) When warning alarms are set, please set return value correctly, otherwise alarm may not work normally. At setting over
high warnings, return value shall be less than set value; At setting over low warnings, return value shall be more than set
value.
3) At successful crank, try to set Gen frequency as low as possible, so that starter can be separated quickly when genset
started.
4) Flexible input ports cannot be set to the same items, otherwise incorrect functions may occur; flexible output ports can be
set to the same items.
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
2020-02-20
Version 1.0
Page 54 of 69

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm8110dc-1

Table of Contents