No.
Warn
20
Temp. Sensor Open
21
High Temp.
22
Low Temp.
Oil
Pressure
23
Open
24
Low Oil Pressure
25
Level Sensor Open
26
Low Level
27
Flexible Sensor 1 Open
28
Flexible Sensor 1 High
29
Flexible Sensor 1 Low
30
Flexible Sensor 2 Open
31
Flexible Sensor 2 High
32
Flexible Sensor 2 Low
33
Digital Input
34
GSM Comm. Fail
35
Earth Fault
HGM9600 Series Genset Controller User Manual
select enable, it will send warn signal.
When controller detects the sensor is open circuit, and the action
select "warn", it will send warn signal.
When controller detects the temperature is higher than the set value,
it will send warn signal.
When controller detects the temperature is lower than the set value, it
will send warn signal.
Sensor
When controller detects the sensor is open circuit, and the action
select "warn", it will send warn signal.
When controller detects the oil pressure is lower than the set value, it
will send warn signal.
When controller detects the sensor is open circuit, and the action
select "warn", it will send warn signal.
When controller detects the oil lever is lower than the set value, it will
send warn signal.
When controller detects the sensor is open circuit, and the action
select "warn", it will send warn signal.
When controller detects the sensor value is higher than the max. set
value, it will send warn signal.
When controller detects the sensor value is lower than the min. set
value, it will send warn signal.
When controller detects the sensor is open circuit, and the action
select "warn", it will send warn signal.
When controller detects the sensor value is higher than the max. set
value, it will send warn signal.
When controller detects the sensor value is lower than the min. set
value, it will send warn signal.
When digit input port is set as warning and active, controller sends
corresponding warning signal.
When select GSM enable but the controller couldn't detect GSM
model, controller sends corresponding warning signal.
When controller detects earth current is greater than value of setting,
and the action "Warning" alarm is set, it will send a "warning" alarm
signal.