6.3

TRIP AND STOP ALARM

When controller detects trip and stop alarm signal, it will shut down generator quickly and stop after high
speed cooling.
No.
Trip and Stop
1
Over Current
2
Maintenance Due
3
Reverse Power
4
Over Power
5
Digital Input
6
Earth Fault
6.4

TRIP ALARM

When controller detects trip alarm, it will break close generator signal quickly, but genset not stop.
No.
Trip
1
Over Current
2
Reverse Power
3
Over Power
4
Digital Input
5
Earth Fault
HGM9600 Series Genset Controller User Manual
Table 10 Trip and Stop Alarm
When controller detects the value is higher than the set value, and the
action select "trip and stop", it will send trip and stop signal.
When count down time is 0 and the action select "trip and stop", it will
send a trip and stop signal.
When controller detects reverse power value (power is negative) is lower
than the set value, and the action select "trip and stop", it will send a trip
and stop signal.
When controller detects the over power value (power is positive) is higher
than the set value, and the action select "trip and stop", it will send a trip
and stop signal.
When digital input port is set as "trip and stop", and the action is active, it
will send a trip and stop signal.
When controller detects the earth current is higher than the set value, and
the action select "trip and stop", it will send a trip and stop signal.
Table 11 Trip Alarm
When controller detects the value is higher than the set value, and the
action select "trip", it will send trip signal.
When controller detects reverse power value (power is negative) is lower
than the set value, and the action select "trip", it will send a trip signal.
When controller detects the over power value (power is positive) is higher
than the set value, and the action select "trip", it will send a trip signal.
When digital input port is set as "trip", and the action is active, it will send
a trip signal.
When controller detects the earth current is higher than the set value, and
the action select "trip", it will send a trip signal.