AUTO START/STOP OPERATION

Press
, its indicator lights, and controller enters Auto mode.
Starting Sequence,
1.
HGM9620: When mains power is abnormal (over and under voltage, over and under frequency, loss of
phase, phase sequence wrong), it enters mains "abnormal delay" and LCD display count down time.
When mains abnormal delay is over, it enters into "start delay"; it also enters this mode when "remote
start on load" is active.
2.
HGM9610: Generator enters "start delay" as soon as "remote start on load" is active.
3.
Start Delay timer is shown on Status page of LCD.
4.
When start delay is over, preheat relay outputs (if this be configured), "preheat start
delay XX s" is shown at the bottom line of LCD.
5.
When preheat delay is over, fuel relay outputs 1s and then start relay output; if engine crank fails
HGM9600 Series Genset Controller User Manual
00008
00008
can exit setting directly during configuration.
Form 5:
Press
to change cursor position,
are used for changing cursor value,
setting (form 4),
Form 6:
are used for changing the setting
contents.
Confirm setting (form 4),
return to previous menu. (form 1).
Confirm
exit setting (form 4).