Scopes And Definitions Of Programmable Parameters; Contents And Scopes Of Parameters - Smartgen HGM9600 Series User Manual

Genset controller
Table of Contents

Advertisement

8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS

8.1

CONTENTS AND SCOPES OF PARAMETERS

No.
Items
Mains Setting
1
AC System
2
Rated Voltage
3
Rated Frequency
4
Normal Time
5
Abnormal Time
6
Volt. Trans.(PT)
7
Over Voltage
8
Under Voltage
9
Over Frequency
10
Under Frequency
11
Loss of Phase
12
Reverse Phase
Timer Setting
1
Start Delay
2
Return Delay
3
Preheat Delay
4
Cranking Time
5
Crank Rest Time
HGM9600 Series Genset Controller User Manual
Table 13 Parameter Setting Contents and Scopes
Parameters
(0~3)
(30~30000)V
(10.0~75.0)Hz
(0~3600)s
(0~3600)s
(0~1)
(0~200)%
(0~200)%
(0~200)%
(0~200)%
(0~1)
(0~1)
(0~3600)s
(0~3600)s
(0~3600)s
(3~60)s
(3~60)s
Defaults
0: 3P4W; 1: 3P3W;
0
2: 2P3W; 3: 1P2W.
Provide standard for checking mains
over/under voltage. (It is primary voltage
when using voltage transformer; it is line
230
voltage when AC system is 3P3W while it
is phase voltage when using other AC
system).
Provide standard for checking mains
50.0
over/under frequency.
10
The delay from mains abnormal to normal.
5
The delay from mains normal to abnormal.
0
0: Disable;
Setting value is mains rated voltage's
percentage, and return value (default:
120%
116%) and delay value (default: 5s) can be
set.
Setting value is mains rated voltage's
80%
percentage, and return value (default: 84%)
and delay value (default: 5s) can be set.
Setting value is mains rated frequency's
114%
percentage, return value (default: 110%)
and delay value(default: 5s) can be set.
Setting value is mains rated frequency's
90%
percentage, return value (default: 94%) and
delay value(default: 5s) can be set.
1
0: Disable;
1
Time from mains abnormal or remote start
1
signal is active to start genset.
Time from mains normal or remote start
1
signal is deactivated to genset stop.
Time of pre-powering heat plug before
0
starter is powered up.
8
Time of starter power up.
10
The waiting time before second power up
Description
1: Enable
1: Enable
Page 32 of 73

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm9610Hgm9620

Table of Contents