Smartgen HGM9600 Series User Manual page 37

Genset controller
Table of Contents

Advertisement

No.
Items
1
GSM Enable
2
Phone Number
Scheduling And Maintenance Setting
1
Scheduled Run
Scheduled
2
Run
3
Maintenance
Analog Sensors Setting
Temperature Sensor
1
Curve Type
Open Circuit
2
Action
High
Temp.
3
Shutdown
4
High Temp. Warn
Low
Temp.
5
Warn
Oil Pressure Sensor
1
Curve Type
Open
Circuit
2
Action
Low
3
Shutdown
4
Low OP Warn
Liquid Level Sensor
1
Curve Type
Open
Circuit
2
Action
HGM9600 Series Genset Controller User Manual
Parameters
(0~1)
Max.20 digits
(0~1)
Not
(0~1)
(0~1)
(0~15)
(0~2)
(-50~+300)ºC
(-50~+300)ºC
(0~1)
(0~15)
(0~2)
OP
(0~1000)kPa
(0~1000)kPa
(0~15)
(0~2)
Defaults
0
0: Disable; 1: Enable
0: Disable; 1: Enable
Its national and area's cods must be
0
added. e.g. China: 8613666666666. Users
can set max. 5 phone numbers.
0
0: Disable; 1: Enable
0
0: Disable; 1: Enable
0
0: Disable; 1: Enable
7
SGX
See Table 16.
0
0: Warn; 1: Shutdown; 2: No action
Shutdown
higher than this value. Detecting only after
98
safety delay is over. The delay value
(default: 3s) also can be set.
Warn when sensor temperature higher
than this value.
95
safety delay is over. The delay value
(default: 5s) and return value (default: 93)
also can be set.
0
0: Disable; 1: Enable
7
SGX. See Table 16.
0
0: Warn 1: Shutdown 2: No action
Shutdown when oil pressure lower than
this value. Detecting only after safety delay
103
is over. The delay value (default: 3s) also
can be set.
Warn when oil pressure higher than this
value. Detecting only after safety delay is
124
over. The delay value (default: 5s) and
return value (default: 138) also can be set.
4
SGH. See Table 16.
0
0: Warn; 1: Shutdown; 2: No action
Description
when
sensor
temperature
Detecting only after
Page 37 of 73