6 PROTECTION

6.1

WARNINGS

When controller detects the warning signal, alarm only and not stop genset.
No.
Warn
1
Over Speed
2
Under Speed
3
Loss of Speed Signal
4
Gen Over Frequency
5
Gen Under Frequency
6
Gen Over Voltage
7
Gen Under Voltage
8
Gen Over Current
9
Fail to Stop
10
Charge Alt Fail
11
Battery Over Voltage
12
Battery Under Voltage
13
Maintenance Due
14
Reverse Power
15
Over Power
16
ECU Warn
17
Gen Loss of Phase
Gen Phase Sequence
18
Wrong
19
Switch Fail Warn
HGM9600 Series Genset Controller User Manual
Table 8 Warnings
When controller detects the speed is higher than the set value, it will
send warn signal.
When controller detects the speed is lower than the set value, it will
send warn signal.
When controller detects the speed is 0 and the action select "Warn",
it will send warn signal.
When controller detects the frequency is higher than the set value, it
will send warn signal.
When controller detects the frequency is lower than the set value, it
will send warn signal.
When controller detects the voltage is higher than the set value, it will
send warn signal.
When controller detects the voltage is lower than the set value, it will
send warn signal.
When controller detects the current is higher than the set value, it will
send warn signal.
When generator not stops after the "stop delay" is over.
When controller detects the charger voltage is lower than the set
value, it will send warn signal.
When controller detects the battery voltage is higher than the set
value, it will send warn signal.
When controller detects the battery voltage is lower than the set
value, it will send warn signal.
When count down time is 0 and the action select "Warn", it will send
warn signal.
When controller detects the reverse power value (power is negative)
is lower than the set value, it will send warn signal.
When controller detects the reverse power value (power is positive)
is higher than the set value, it will send warn signal.
When controller gets the alarm signal from engine via J1939, it will
send warn signal.
When controller detects the generator loss phase, it will send warn
signal.
When controller detects the reverse phase, it will send warn signal.
When controller detects the switch on and off fail, and the action
Description