when operator decides that the engine has fired, he/she should release the button and start output will be deactivated,
safety on delay will start.
CAUTION: Default password is 00318, user can change it in case of others change the advanced parameters setting.
Please clearly remember the password after changing. If you forget it, please contact SmartGen services and send all
information in the controller page of "ABOUT" to us.
5.3

LCD DISPLAY

5.3.1

MAIN DISPLAY

Main screen show pages; use
★Main Screen, including as below,
Gen: voltage, frequency, current, active power, reactive power
Bus: voltage, frequency
Engine: speed
Some status.
★Status, including as below,
Status of genset, mains, and ATS.
NOTE: HGM9610 has no mains status screen.
★Engine, including as below,
Speed, temperature of engine, engine oil pressure, (fuel) level, configure sensor 1, configure sensor 2,
battery voltage, charger voltage, accumulated run time, accumulated start times.
NOTE: If connected with J1939 engine via CANBUS port, this page also includes: coolant pressure, coolant level, fuel
temperature, fuel pressure, inlet temperature, exhaust temperature, turbo pressure, total fuel consumption and so on.
(Different engine with different parameters)
★Gen, including as below,
Phase voltage, Line voltage, frequency, phase sequence.
★Mains, including as below,
Phase voltage, Line voltage, frequency, phase sequence.
NOTE: HGM9610 has no this page.
★Load, including as below,
Current, each phase and total active power (positive and negative), each phase and total reactive power
(positive and negative), each phase and total apparent power, each phase and average power factor
(positive and negative), accumulated energy (kWh, kvarh, kVAh) and earth current.
NOTE: When only mains switch on indicator lights, count active and inactive power, apparent power, power factor, but
accumulate electric energy. Counting the generator active and reactive power, apparent power, power factor, and accumulate
electric energy under other conditions.
HGM9600 Series Genset Controller User Manual
to scroll the pages and
to scroll the screen.