10 SENSORS SETTING

1.
When reselect sensors, the sensor curve will be transferred into the standard value. For example, if
temperature sensor is SGX (120°C resistor type), its sensor curve is SGX (120°C resistor type); if
select the SGD (120°C resistor type), the temperature sensor curve is SGD curve.
2.
When there is difference between standard sensor curves and using sensor, user can adjust it in
"curve type".
3.
When input the sensor curve, X value (resistor) must be input from small to large, otherwise, mistake
occurs.
4.
If select sensor type as "None", sensor curve is not working.
5.
If corresponding sensor has alarm switch only, user must set this sensor as "None", otherwise, maybe
there is shutdown or warning.
6.
The headmost or backmost values in the vertical coordinates can be set as same as below,
1Pa
2
1kgf/cm
1bar
1psi
HGM9600 Series Genset Controller User Manual
Fig.4 Sensor Curve
Table 18 Normal Pressure Unit Conversion
pa
1
1.02x10
4
9.8x10
1x10
5
6.89x10
3
7.03x10
2
kgf/cm
5
1
1.02
2
6.89x10
bar
1x10
5
1.45x10
0.98
1
2
Page 52 of 73
psi
4
14.2
14.5
1