No.
Items
3
Rated Voltage
4
Loading Voltage
5
Rated Frequency
Loading
6
Frequency
7
Volt. Trans.(PT)
Over
Volt.
8
Shutdown
Under
Volt.
9
Shutdown
Over
Freq.
10
Shutdown
Under
Freq.
11
Shutdown
12
Over Volt. Warn
Under
Volt.
13
Warn
14
Over Freq. Warn
15
Under Freq. Warn
16
Loss of Phase
HGM9600 Series Genset Controller User Manual
Parameters
Defaults
(30~30000)V
(0~200)%
(10.0~75.0)Hz
(0~200)%
(0~1)
(0~200)%
(0~200)%
(0~200)%
(0~200)%
(0~200)%
(0~200)%
(0~200)%
(0~200)%
(0~1)
without speed sensor.
To offer standards for detecting of
generator' over/under voltage and loading
voltage. (It is primary voltage when using
230
voltage transformer; it is line voltage when
AC system is 3P3W while it is phase
voltage when using other AC system).
Setting value is percentage of generator
rated voltage. Detect when controller ready
85%
to loading. If generator voltage under load
voltage, won't enter into normally running.
To offer standards for detecting of
50.0
over/under/load frequency.
Setting value is percentage of generator
rated
frequency.
85%
frequency under load frequency, it won't
enter into normal running.
0
0: Disable;
120%
Setting value is percentage of generator
rated volt. Delay value (default: 3s) also
80%
can be set.
Setting value is percentage of generator
114%
rated freq. Delay value (default: 2s) also
can be set.
Setting value is percentage of generator
80%
rated freq. Delay value (default: 3s) also
can be set.
Setting value is percentage of generator
rated volt. Delay value(default: 5s) and
110%
return value(default: 108%) also can be
set.
Setting value is percentage of generator
84%
rated volt. Delay value (default: 5s) and
return value (default: 86%) also can be set.
Setting value is percentage of generator
rated freq. Delay value (default: 5s) and
110%
return value (default: 108%) also can be
set.
Setting value is percentage of generator
84%
rated freq. Delay value (default: 5s) and
return value (default: 86%) also can be set.
1
0: Disable 1: Enable
Description
When
generator
1:Enable
Page 35 of 73