Smartgen HGM9600 Series User Manual page 27

Genset controller
Table of Contents

Advertisement

No.
Shutdown
19
Low Oil Pressure
20
Level Sensor Open
21
Flexible Sensor 1 Open
22
Flexible Sensor 1 High
23
Flexible Sensor 1 Low
24
Flexible Sensor 2 Open
25
Flexible Sensor 2 High
26
Flexible Sensor 2 Low
27
Digital Input Port
28
Earth Fault
HGM9600 Series Genset Controller User Manual
When controller detects oil pressure is lower than the set value, it
will send a stop signal.
When controller detects sensor is open circuit, and the action select
"shutdown", it will send a stop signal.
When controller detects sensor is open circuit, and the action select
"shutdown", it will send a stop signal.
When controller detects the sensor value is higher than the max. set
value, it will send stop signal.
When controller detects the sensor value is lower than the min. set
value, it will send stop signal.
When controller detects sensor is open circuit, and the action select
"shutdown", it will send a stop signal.
When controller detects the sensor value is higher than the max. set
value, it will send stop signal.
When controller detects the sensor value is lower than the min. set
value, it will send stop signal.
When digital input port is set as shutdown, and the action is active, it
will send a shutdown signal.
When controller detects the earth current is higher than the set value,
and the action select "shutdown", it will send stop signal.
Description
Page 27 of 73