Smartgen HGM9600 Series User Manual page 47

Genset controller
Table of Contents

Advertisement

No.
Type
18
Auto Mode Invalid
19
Reserved
20
Reserved
21
Inhibit Alarm Stop
22
Aux Instrument Mode
23
Reserved
24
Reset Maintenance
25
Reserved
26
Aux. High Temp
27
Aux. Low OP
28
Remote Start (On Load)
29
Remote Start (Off Load)
30
Aux. Manual Start
31
Reserved
32
Reserved
33
Simulate Stop key
34
Simulate Manual key
35
Reserved
36
Simulate Auto key
37
Simulate Start key
38
Simulate G-Load key
39
Simulate M-Load key
40
Reserved
41
Reserved
42
Reserved
43
Reserved
HGM9600 Series Genset Controller User Manual
keys except
When input is active, controller won't work under Auto mode.
key and simulate auto key input does not work.
All shutdown alarms are prohibited except emergence
stop.(Means battle mode)
All outputs are prohibited in this mode.
Controller will set maintenance time and date as default when
input is active.
Connected sensor digital input.
Connected sensor digital input.
In Auto mode, when input active, genset can be started
automatically and take load after genset normal running; when
input inactive, genset will stop automatically.
In Auto mode, when input is active, genset can be started
automatically and NOT take load after genset normal running;
when input is inactive, genset will stop automatically.
In Manual mode, when input active, genset will start
automatically;
when
automatically.
An external button can be connected and pressed as simulate
panel.
An external button can be connected and pressed as simulate
panel.
This is simulate G-close key when HGM9610 controller is
applied.
This is simulate M-open key when HGM9610 controller is
applied.
Description
are inactive.
input
inactive,
genset
will
stop
Page 47 of 73