NOTE: Overcurrent setting details about definite time delay and inverse definite minimum time are as follows:
Definite Time: Overcurrent delay is definite time delay. Different overcurrent value has corresponding delay.
Inverse Definite Minimum Time (IDMT): Overcurrent delay decrease with the increase of overcurrent. Different
overcurrent value has corresponding delay.
IDMT formula:
T = t / ((IA/IT)-1)
2
T: Overcurrent delay (second)
t: Timing multiplier ratio
IA: Current max. load current (L1/L2/L3)
IT: Overcurrent setting value
Example:
t = 36
IA = 550A
IT =500A
Conclusion: T = 3600s (1hour)
HGM9600 Series Genset Controller User Manual
Parameters
Defaults
(0~239)
(0~1)
(0~239)
(0~1)
(0~239)
(0~1)
(0~239)
(0~1)
29
Generator closed output. See Table 14.
0: Normally open;
0
1: Normally close
31
Mains closed output. See Table 14.
0: Normally open;
0
1: Normally close
38
ETS solenoid hold. See Table 14.
0: Normally open;
0
1: Normally close
48
Common alarm. See Table 14.
0: Normally open;
0
1: Normally close