13.12 MTU ADEC (SMART MODULE)

It is suitable for MTU engine with ADEC (ECU8) and SMART module.
Terminals of controller
Programmable output 1
Starting relay output
Terminals of controller
CAN_SCR
CAN(H)
CAN(L)
Engine type: MTU-ADEC.

13.13 MTU ADEC (SAM MODULE)

It is suitable for MTU engine with ADEC (ECU7) and SAM module.
Terminals of controller
Programmable output 1
Starting relay output
Terminals of controller
CAN_SCR
CAN(H)
CAN(L)
Engine type: Common J1939.
HGM6100LT Series Genset Controller User Manual
Table 29 – ADEC (X1 port)
ADEC (X1 port)
X1 10
X1 34
Table 30 – SMART (X4 port)
SMART (X4 port)
X4 3
X4 1
X4 2
Table 31 – ADEC (X1 port)
ADEC (X1 port)
X1 43
X1 37
Table 32 – SAM (X23 port)
SAM (X23 port)
X23 3
X23 2
X23 1
Remark
Set programmable output 1 as "Fuel
Output".
X1 Terminal 9 Connected to negative of
battery.
X1 Terminal 33 Connected to negative of
battery.
Remark
CAN communication shielding line.
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Remark
Set programmable output 1 as "Fuel
Output".
X1 Terminal 28 Connected to negative of
battery.
X1 Terminal 22 Connected to negative of
battery.
Remark
CAN communication shielding line.
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Page 46 of 50