13.4 CUMMINS QSZ13
Terminals of controller
Aux. output 1
Aux. output 2
CAN(H)
CAN(L)
Engine type: Cummins-QSZ13.
13.5 DEUTZ EMR2
Terminals of controller
Aux. output 1
Aux. output 2
-
CAN(H)
CAN(L)
Engine type: DEUTZ-EMR2.
13.6 MTU ADEC (SMART MODULE)
Suitable for MTU engine with ADEC (ECU8) and SMART module.
Terminals of controller
Aux. output 1
Aux. output 2
Terminals of controller
CAN(H)
CAN(L)
Engine type: MTU-ADEC.
HEM4300 Engine Controller User Manual
Table 22 Engine OEM Connector
OEM connector of engine
45
-
1
21
Table 23 F Connector
F connector
Expansion
30A
providing battery voltage
for 14; Fuse is 16A.
-
1
12
13
Table 24 ADEC (X1 Port)
ADEC (X1port)
X1 10
X1 34
Table 25 ADEC (X4 Port)
SMART (X4 port)
X4 1
X4 2
Oil injection switch. Configure it as "Fuel
Output".
Configure it as "Crank Output". Connect to
starter coil directly via expand relay.
Using twisted-pair shielded line with single
end grounded.
relay,
Configure it as "Fuel Output".
Configure it as "Crank Output". Connect to
starter coil directly via expand relay.
Connect to battery negative pole.
Using twisted-pair shielded line with single
end grounded.
Configure it as "Fuel Output".
X1 Terminal 9 connected to negative of
battery.
X1 Terminal 33 connected to negative of
battery.
Using twisted-pair shielded line with single
end grounded.
Remark
Remark
Remark
Remark
Page 52 of 55