Mitsubishi Electric MELSERVO MR-J2-A Product Specifications And Installation Manual page 68

Servo motors and servo amplifiers
Table of Contents

Advertisement

2. OPERATION
Class No. Symbol
14
TQC
Torque command time constant:
Used to set the constant of a low pass filter in response
to the torque command.
Torque
For manufacturer setting
15
Must not be change.
16
*BPS
Communication baudrate selection, alarm history clear:
Used to select the communication baudrate for use of
the set-up software and to clear the alarm history.
0
Name and Function
Torque command
TQC
TQC: Torque command time constant
0
Selection of baudrate for RS-232C
0: 9600
[bps]
1: 19200 [bps]
Alarm history clear
0: Invalid
1: Valid
When alarm history clear is made
valid, the alarm history is cleared
at next power-on. After the alarm
history is cleared, the setting is
automatically made invalid (reset to 0).
2– 37
Initial
Unit
Value
ms
0
After
filtered
TQC
Time
0
0000
Control
Setting
Range
Mode
0 to 20000
T
0000h
P • S • T
to
0011h
2