6. OPTIONS AND AUXILIARY EQUIPMENT
(3) Connection of the regenerative brake option
When using the regenerative brake option, always remove wiring from
across P-D and install the regenerative brake option across P-C. Set
parameter No.0 according to the option to be used. The regenerative
brake option will generate heat of about 100°C. Fully examine heat
dissipation, installation position, used cables, etc. before installing
the option. For wiring, use fire-retarding cables and keep them clear
of the regenerative brake option body. Always use twisted cables of
max. 5m length for connection with the servo amplifier.
Servo amplifier
Note: Make up a sequence which will switch off the magnetic contactor
(MC) when abnormal heating occurs.
CAUTION
Regenerative brake option
D
P
C
(Note)
5m (16.4 ft) max.
Always remove the
lead from across P-D.
P
C
G3
G4
6– 4
Parameter No. 0
Selection of regenerative
brake option
0: Not used.
2: MR – RB 032
3: MR – RB 12
4: MR – RB 32
5: MR – RB 30
6: MR – RB 50
G3 • G4: Thermal protector terminals.
Abnormal heating will dis-
connect G3-G4.