8.1

Wiring of External Power Supply

Separating the power supply system
Carry out wiring so that the power supply system is separated into the GOT, I/O equipment, and power equipment as shown
below.
When frequent noise is identified, connect an isolation transformer.
Isolation
GOT
transformer
power
Main power
T1
I/O power
Main circuit power
Separating the power cables from the main circuit line and the I/O signal line
Separate the 24 V DC cables from the main circuit lines (high voltage, large current) and I/O signal lines.
Keep a distance of 100 mm or more between them as a guide.
Treatment on power cables
Twist the 24 V DC cables as closely as possible, and connect the cables with the minimum length between the power supply
and each device.
Use a thick wire (cross-sectional area: about 0.75 mm
Use the solderless terminal for M3, and tighten the terminal firmly with a torque of 0.5 N•m to 0.8 N•m.
GOT
I/O equipment
Main circuit equipment
2
2
to 2 mm
) for less voltage drop.