15
SPECIFICATIONS
15.1

General Specifications

Item
*1
Operating ambient temperature
Storage ambient temperature
Operating/storage ambient humidity
Vibration resistance
Shock resistance
Operating atmosphere
*3
Operating altitude
Installation location
*4
Overvoltage category
*5
Pollution degree
Cooling method
Grounding
*1 Includes the temperature inside the enclosure of the control panel on which the GOT is installed.
*2 If the ambient temperature exceeds 40°C, the absolute humidity must not exceed 90% RH at 40°C.
*3 Do not use or store the GOT under pressures higher than the atmospheric pressure of altitude 0 m (0 ft.). Failure to observe this
instruction may cause a malfunction. When the air inside the control panel is purged by pressurization, the surface sheet may be lifted
by high pressure. As a result, the touch panel may be difficult to press, and the sheet may be peeled off.
*4 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within the premises. Category II applies to equipment for which electrical power is supplied from
fixed facilities. The surge voltage withstand level for up to the raged voltage of 300 V is 2500 V.
*5 This index indicates the degree to which conductive pollution is generated in the environment where the equipment is used. In pollution
degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.
Specifications
0 to 50°C
-20 to 60°C
10% RH to 90% RH, non-condensing
Conforms to IEC
61131-2
Under
intermittent
vibration
Under
continuous
vibration
2
Conforms to IEC 61131-2 (147 m/s
, 3 times each in the X, Y, and Z directions)
No greasy fumes, corrosive gas, flammable gas, excessive conductive dust, and direct sunlight (as well as at storage)
2000m (6562ft) max.
Inside control panel
II or less
2 or less
Self-cooling
Grounding with a ground resistance of 100 Ω or less by using a ground cable that has a cross-sectional area of 2
2
mm
or more. If impossible, connect the ground cable to the control panel.
*2
Frequency
Acceleration
5 to 8.4 Hz
-
2
8.4 to 150 Hz
9.8 m/s
5 to 8.4 Hz
-
2
8.4 to 150 Hz
4.9 m/s
Half amplitude
Sweep Count
3.5 mm
10 times each in
X, Y and Z
-
directions