Use a small driver with a straight, untapered blade as shown below to tighten the power terminals.
Use a driver
with a flat end
0.6 mm
3.5 mm
Manufacturer
Phoenix Contact Inc.

Wiring example

Connect the power supply to the power terminals on the back panel of the GOT.
Class D
grounding
+10%
DC24V
- 15%
Tightening torque for the power terminals: 0.5 to 0.6 N·m

GOT's ground

Grounding the GOT and other devices
Make sure to carry out the followings for grounding.
• Carry out the independent grounding if possible. Provide class D (class 3) grounding. (Ground resistance must be 100 Ω or
less.)
• If the independent grounding is impossible, carry out the shared grounding as shown in fig.2) below.
Other
GOT
device
Grounding
(100 Ω or less)
(1) Independent ground
...... Best condition
2
• Use the cable of 2 mm
or longer for grounding. Set the ground point as close to the GOT as possible to shorten the
grounding cable.
Model
SZS 0.6
Other
GOT
device
Grounding
(100 Ω or less)
(2) Shared grounding
...... Good condition
3.5
Other
GOT
device
(3) Common grounding
...... Not allowed