The following tables list the distance required between the GOT and the other devices.
The dimensions within the parentheses apply when no equipment generating radiated noise (such as a contactor) or heat is
installed near the GOT.
However, always keep the ambient temperature of the GOT to 50 °C or lower.
Unit: mm (inch)
Item
A
B
C
D
*1
E
*1 When opening or closing the battery cover: 72 (2.83) or more.
7 INSTALLATION AND REMOVAL
68
7.3 Installation Position
GS2512-WXTBD
51 (2.01) or more
[23 (0.91) or more]
Horizontal: 81 (3.19) or more [23(0.91) or more]
Vertical: 53 (2.09) or more [23(0.91) or more]
53 (2.09) or more
[23 (0.91) or more]
Horizontal: 53 (2.09) or more [23(0.91) or more]
Vertical: 81 (3.19) or more [23(0.91) or more]
100 (3.94) or more
[20 (0.79) or more]