6 Wiring and Connecting

6.2 Wiring to the Power Supply Module

The following diagram shows the wiring example of power lines, grounding lines, etc. to the basic base unit and the
extension base unit.
For wiring examples for each power supply module, refer to the manual included with the power supply module.

6.2.1 R61P/R62P/R63P/R64P

[AC power supply]
100/200VAC
AC
AC
DC
24VDC
*1
100/200VAC
*1: Connected to the 24VDC terminal of a module that requires a supply of 24VDC inside an I/O module.
(Note 1) Use the possibly thickest (up to 2 mm
terminals for the terminal block wiring. To prevent a short circuit caused by any loosen screws, use 0.8mm
thick crimp terminals with insulation sleeves. Up to 2 terminals can be attached to a terminal area.
(Note 2) Ground the LG and FG terminals after short-circuiting them. If LG (PE) terminals and FG terminals are
connected without grounding the wires, the modules may be susceptible to noise. In addition, since the LG
terminals have potential of 1/2 input voltage, the operator may receive an electric shock when touching metal
parts.
IB-1501452-C
R04CPU
R61P
ERR
FG
LG
INPUT
100-240VAC
R61P
ERR
FG
LG
INPUT
100-240VAC
2
) wires for the 100/200 VAC and 24 VDC power cables. Always use crimp
[DC power supply]
24VDC
AC
24VDC
76
R04CPU
R63P
ERR
FG
LG
INPUT
+24V
24G
R63P
ERR
FG
LG
INPUT
+24V
24G