33.1

Daily Inspection

Daily inspection items
Item
Inspection Item
1
GOT mounting status
2
Connection
Loose terminal screws
status
Proximate solderless
terminals
Loose connectors
3
Usage status
Foreign material
attachment
33.2

Periodic Inspection

Yearly or half-yearly inspection items
The following inspection should also be performed when equipment has been moved or modified or the wiring changed.
Item
Inspection Item
1
Surrounding
Ambient temperature
environment
Ambient humidity
Atmosphere
2
Power supply voltage check
3
Mounting
Looseness
status
Foreign material
attachment
4
Connection
Loose terminal screws
status
Proximate solderless
terminals
Loose connectors
33 MAINTENANCE AND INSPECTION
396
33.1 Daily Inspection
Inspection Method
Criterion
Check for loose mounting
Securely mounted
screws.
Retighten screws with
Not loose
screwdriver
Visual check
Proper space
Visual check
Not loose
Visual check
No foreign matter sticking
Inspection Method
Criterion
Make measurement with
0 to 50°C
thermometer or hygrometer.
10 to 90%RH
Measure corrosive gas.
No corrosive gas
Measure the voltage
20.4 to 26.4 V DC
between 24 V DC terminals.
Move module
Should be mounted firmly
Visual check
No foreign matter sticking
Retighten screws with
Not loose
screwdriver
Visual check
Proper space
Visual check
Not loose
Corrective action
Retighten screws within the specified
torque range
Retighten terminal screws
Correction
Retighten connector fixing screws
Remove, clean
Action
For use in control panel, temperature
inside control panel is ambient
temperature
Change supply power
Retighten screws
Remove, clean
Retighten terminal screws
Correction
Retighten connector fixing screws