Periodic Inspection - Mitsubishi Electric GOT SIMPLE Series Operation Manual

Hide thumbs Also See for GOT SIMPLE Series:
Table of Contents

Advertisement

10.2

Periodic Inspection

Half-yearly or yearly inspection items
Inspect the following items when moving or modifying equipment, or changing wiring.
Item
Inspection item
1
Surrounding
Ambient temperature
environment
Ambient humidity
Atmosphere
2
Input polarity of 24 V DC power
3
Installation
Looseness
status
Foreign material
adherence
4
Connection
Loose terminal screws
status
Proximity of solderless
terminals
Loose contactors
5
Battery
*1 The criterion varies with the installation orientation.
For the details, refer to the following.
Page 69 Control Panel Inside Temperature and GOT Installation Angle
Inspection method
Criterion
Measure corrosive gas
Display section
with a thermometer or
Other sections
hygrometer.
10 % RH to 90% RH
No corrosive gas
Measure voltage across
Connected according to terminal
24 V DC terminals.
markings on the GOT power
supply section
Move the unit.
Mounted firmly
Visual check
No foreign matter adherence
Retighten screws with a
Not loose
screwdriver.
Visual check
Proper intervals
Visual check
Not loose
Check the voltage status
No alarm
of the GOT built-in
battery in [Time] of the
utility.
GOT2000 Series
User's Manual (Utility)
Corrective action
0 °C to 40 °C
For use in a control panel, the control
panel inside temperature is the
*1
ambient temperature.
Change wiring.
Retighten screws.
Remove the foreign material and
clean.
Retighten terminal screws.
Correct intervals.
Retighten contactor fixing screws.
Replace the battery with a new battery
when the current battery has reached
the specified life span, even if the low
voltage is not indicated.
10 MAINTENANCE AND INSPECTION
10.2 Periodic Inspection
10
101