Commissioning
Parameter
Assign process variable
On value low flow cutoff
Off value low flow cutoff
Pressure shock suppression
68
10.2.9
Configuring the low flow cut off
The Low flow cut off submenu contains parameters that must be configured for the
configuration of low flow cut off.
Navigation
"Setup" menu → Low flow cut off
Low flow cut off
Parameter overview with brief description
Prerequisite
–
One of the following options is
selected in the Assign process
variable parameter:
• Mass flow
• Volume flow
• Corrected volume flow
One of the following options is
selected in the Assign process
variable parameter:
• Mass flow
• Volume flow
• Corrected volume flow
One of the following options is
selected in the Assign process
variable parameter:
• Mass flow
• Volume flow
• Corrected volume flow
→
Assign process variable
On value low flow cutoff
Off value low flow cutoff
Pressure shock suppression
Description
Select process variable for low
flow cut off.
Enter on value for low flow cut
off.
Enter off value for low flow cut
off.
Enter time frame for signal
suppression (= active pressure
shock suppression).
Proline Cubemass C 100 HART
Selection / User
Factory setting
entry
• Off
Mass flow
• Mass flow
• Volume flow
• Corrected volume
flow
Positive floating-
For liquids: depends
point number
on country and
nominal diameter
0 to 100.0 %
50 %
0 to 100 s
0 s