10.5.12 Configuring The Low Flow Cut Off - Endress+Hauser Proline Promass H 300 PROFINET Operating Instructions Manual

Coriolis flowmeter
Table of Contents

Advertisement

Proline Promass H 300 PROFINET
Parameter
Assign process variable
On value low flow cutoff
Off value low flow cutoff
Pressure shock suppression
*
Visibility depends on order options or device settings
Endress+Hauser

10.5.12 Configuring the low flow cut off

The Low flow cut off wizard systematically guides the user through all the parameters
that must be set to configure low flow cut off.
Navigation
"Setup" menu → Low flow cut off
Low flow cut off
Assign process variable
On value low flow cutoff
Off value low flow cutoff
Pressure shock suppression
Parameter overview with brief description
Prerequisite
A process variable is selected
in the Assign process variable
parameter (→  113).
A process variable is selected
in the Assign process variable
parameter (→  113).
A process variable is selected
in the Assign process variable
parameter (→  113).
Description
Select process variable for low
flow cut off.
Enter on value for low flow cut
off.
Enter off value for low flow cut
off.
Enter time frame for signal
suppression (= active pressure
shock suppression).
Commissioning
→  113
→  113
→  113
→  113
Selection / User
Factory setting
entry
• Off
Mass flow
• Mass flow
• Volume flow
• Corrected volume
*
flow
Positive floating-
Depends on country
point number
and nominal
diameter
0 to 100.0 %
50 %
0 to 100 s
0 s
113

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Proline Promass H 300 PROFINET and is the answer not in the manual?

Table of Contents