HUAWEI NetEngine80E Router
Installation Guide
No.
3
4
5
6
Issue 02 (2011-09-10)
Check Item and Description
The installation holes on the support and
feet are fit for the expansion bolts. The
support is insulated from the ground; the
floor holder is insulated from the guide
rails.
The cabinets in the same row are evenly
aligned with each other. Rows of
cabinets are aligned along the main
aisle, with a deviation of up to 5 mm.
The accessories on the front and back
doors of the cabinet are present. A
connecting plate is installed if two
cabinets are attached to each other.
The front door of the cabinet can be
opened and closed smoothly.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Powering on Devices
Method
Check this by measuring the megohm
range of a multimeter. The resistance of
each insulating point must be greater
than 5 megohms.
-
-
Check this by unlocking the door
according to the following figure.
Check this by locking the door
according to the following figure.
91