HUAWEI NetEngine80E Router
Installation Guide
Figure E-2
Figure E-2 Schematic diagram of the DC NEPS5000-D (5 KW)
Table E-2
Table E-2 Current parameters of each circuit breaker and each power line for the PDF (DC
NEPS5000-D (5 KW) )
Item
Each circuit breaker (A1, A2,
A3, B1, B2, and B3)
Each power input (A1, A2,
A3, B1, B2, and B3)
Issue 02 (2011-09-10)
shows the schematic diagram of the DC power module NEPS5000-D (5 KW).
Power Destribution
Frame (PDF)
A1
A2
A3
B1
B2
B3
NOTE
You need to provide 3 DC power lines for the NEPS5000-D. If a device is equipped with double NEPS5000-
D power modules, 6 DC power lines are required. The 6 DC power lines of the power distribution frame
(PDF) are directly connected to power module A and power module B.
shows the current parameters of each circuit breaker and each power line for the PDF
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
a1
a2
Power moudue A
NEPS5000-D
a3
b1
b2
Power moudue B
b3
NEPS5000-D
Specification
≥ 60 A
≥ 44 A @ -48 VDC
E Guide to Power Distribution Design
Note
To protect power supplies of
different levels, it is
recommended that the
current of the circuit breaker
on the user side should be
greater than or equal to that of
the circuit breaker of the
power module (60 A).
To support the maximum
configuration, it is
recommended that each DC
power line should provide a
minimum of 44 A @ -48
VDC current.