Goodrive100 inverters
Function
Name
code
Torque setting
P03.11
method
Keypad setting
P03.12
torque
Torque given
P03.13
filter time
Torque control
forward
P03.14
rotation upper-
limit frequency
setting source
Detailed instruction of parameters
This parameter is used to enable the torque control mode,
and set the torque setting means.
0:Torque control is invalid
1:Keypad setting torque(P03.12)
2:Analog AI1 setting torque
3:Analog AI2 setting torque
4:Analog AI3 setting torque
5:Pulse frequency HDI setting torque
6: Multi-stage torque setting
7:MODBUS communication setting torque
8~10: Reserved
Setting range: -300.0%~300.0%(motor rated current)
0.000~10.000s
0:keypad
setting
P03.14,P03.17 sets P03.15)
1:Analog AI1 setting upper-limit frequency
IKR Aandrijven en Besturen
www.ikr-industries.nl
Keypad operation procedure
upper-limit
frequency(P03.16
Default
Modify
value
0
50.0%
0.100s
sets