Goodrive100 inverters
Function
Name
code
Combination
P00.09
type of the
setting source
Keypad set
P00.10
frequency
P00.11
ACC time 1
Detailed instruction of parameters
setting if it needs to adjust on the base of A frequency
command.
0: A, the current frequency setting is A freauency command
1: B, the current frequency setting is B frequency command
2: A+B, the current frequency setting is A frequency
command + B frequency command
3: A-B, the current frequency setting is A frequency command
- B frequency command
4: Max(A, B):The bigger one between A frequency command
and B frequency is the set frequency.
5: Min(A, B):The lower one between A frequency command
and B frequency is the set frequency.
Note:The
combination
P05(terminal function)
When A and B frequency commands are selected as "keypad
setting", this parameter will be the initial value of inverter
reference frequency
Setting range:0.00 Hz~P00.03(the Max. frequency)
ACC time means the time needed if the inverter speeds up
from 0Hz to the Max. One (P00.03).
DEC time means the time needed if the inverter speeds down