Communication Parameters - Toshiba TOSVERT VF-FS1 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

Communication
Title
No.
0734
0735
0738
0748
0749
*1 : Default values vary depending on the capacity. ⇒ See the table of page K-14.

• Communication parameters

Communication
Title
No.
0800
0801
0802
0803
0805
0806
11
0811
0812
0813
0814
0829
Minimum
setting unit
Function
Unit
Panel/Commun
ication
Prohibition of
-
panel emergency
stop operation
Prohibition of
-
panel reset
operation
Head of
-
parameter display
selection
Integral output
-
power retention
selection
Display unit
-
selection for
integral output
power
Minimum
setting unit
Function
Unit
Panel/Commun
ication
Communication
-
rate
Parity
-
Inverter number
-
Communication
s
error trip time
Communication
s
0.01/0.01
waiting time
Setting of master
-
and slave for
communication
between inverters
Communication
%
command point 1
setting
Communication
Hz
0.1/0.01
command point 1
frequency
Communication
%
command point 2
setting
Communication
Hz
0.1/0.01
command point 2
frequency
Selection of
-
communication
protocol
Adjustment range
-
0: Permitted
1: Prohibited
-
0: Permitted
1: Prohibited
-
0: AUF
1: AUH
-
0: Disabled
1: Enabled
-
0: 1=1kWh
1: 0.1=1kWh
2: 0.01=1kWh
3: 0.001=1kWh
Adjustment range
-
0: 9600bps
1: 19200bps
-
0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
1/1
0-247
1/1
0: Disabled
1-100
0.00: Regular communication
0.01-2.00
-
0: Slave (0 Hz command issued in
case the master inverter fails)
1: Slave (Operation continued in case
the master inverter fails)
2: Slave (Emergency stop tripping in
case the master inverter fails)
3: Master (transmission of frequency
commands)
4: Master (transmission of output
frequency signals)
1/1
0-100
0.0-200.0
1/1
0-100
0.0-200.0
-
0: Toshiba inverter protocol
1: ModbusRTU protocol
2: Metasys N2 protocol
3: APOGEE FLN protocol
4: BAC-net protocol
K-12
E6581381
Default
User
Reference
setting
setting
0
6.20.1
0
0
6.20.7
1
6.20.8
*1
Default
User
Reference
setting
setting
1
6.21
1
0
0
0.00
0
0
6.5.2
6.21
0.0
100
50.0 (WP)
60.0 (WN)
0
6.21

Advertisement

Table of Contents
loading

Table of Contents